Abstract

Measurements of flow-generated noise produced by two different types of strip spoilers in the air duct and radiated from an open exhaust termination unit into a reverberation chamber have been made in 1/3 octave bands using sound power spectra. The measured values are compared with the predicted values using CIBSE Guide B5 method based on selected values of the constant C. It is found that the measured values agree well with the predicted values. The measured values are also compared with the predicted sound power levels using the generic equations given in the Appendix 5.A2 of the CIBSE Guide. It is found that the predicted values using the generic formulae and the single normalised spectrum given in the Appendix 5.A2 of CIBSE Guide do not agree well with the measured values, particularly at low frequencies. For very different in-duct elements, a single normalised spectrum for flow-generated noise may not be sufficient for all configurations of the in-duct elements. It is suggested that several representative normalised spectra for different types of in-duct elements should be given. Practical application: This study provides an evaluation of the accuracy of the CIBSE Guide B5 method and the CIBSE Appendix 5.A2 generic formulae for the prediction of flow-generated noise produced by in-duct spoilers in a ventilation system. It also gives comments on the method for improvements.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.