Abstract

This is a study into the ability of the Fire Dynamics Simulator Version 1.0 (FDS 1.0) to predict smoke detector activation. FDS is a field computer model that has shown promise in the modeling of fire phenomena. Two methods were used to create a first order approximation of the ability of FDS to predict smoke detector activation. First, the fluid transport model of smoke within FDS was tested and compared with full scale UL217 test data. Second, a series of full-scale multicompartment fire tests were conducted to provide a data set to further validate the results obtained from FDS. It was determined that FDS can predict smoke detector activation when used in conjunction with smoke detector lag correlations that correct for the time delay associated with smoke having to penetrate the detector housing.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.