Abstract

Physical–chemical pre-treatment was used for the reverse osmosis unit for reclamation of secondary effluents. The pilot plant was equipped with a variety of tertiary treatment units to prevent fouling and biofouling of the cellulose-acetate reverse osmosis membranes used. The optimisation of pre-treatment involved application of various concentrations of lime to raise the pH to 10.3–12.1, and to stabilise the sludge generated, as well as different dosages of ferric chloride (15, 20, and 25 mg/L) for the coagulation and solid–liquid separation. Sodium hypochlorite (8 mg/L) and UV disinfection are used for microbiological control. The water quality obtained, under the optimum conditions (pH=10.5; FeCl 3: 25 mg/L; anionic flocculant: 0.5 mg/L; sodium hypochlorite: 8 mg/L) was high, showing an average conductivity of 66 μS/cm and low COD values 4 mg O 2/L. The product water is suitable for injection into a groundwater aquifer to counteract seawater intrusion.