Abstract

This paper presents practical energy management system (EMS) models which consider the operational constraints of distributed energy resources, active-reactive power balance, unbalanced system configuration and loading, and voltage dependent loads. A novel linearization approach is proposed and validated based on the fact that, for isolated microgrids, due to the characteristics of feeders, network losses, and voltage drops across feeders are relatively small. The proposed EMS models are mixed integer quadratic programming problems, requiring less computation time and thus suitable for online applications. The practical EMS models are compared with a typical decoupled unit commitment and optimal power flow-based EMS with and without consideration of system unbalancing. The models, along with “standard” EMS models, are tested, validated, and compared using a CIGRE medium voltage benchmark system and the real isolated microgrid of Kasabonika Lake First Nation in Northern Ontario, Canada. The presented results demonstrate the effectiveness and practicability of the proposed models.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.