Abstract
In a biotechnology facility project, the decision was made to require arc resistant medium voltage (MV) switchgear for the safety of operating personnel. The available service voltage was 26.4 kV, limiting the availability of proven designs of arc-resistant switchgear. As a result, the owner considered use of medium voltage gas insulated switchgear (GIS) with vacuum circuit breakers. Once this decision was made, consideration was given to using the same class of switchgear for the 4.16 kV voltage equipment in the facilities. This offered advantages of uniformity, commonality of spares, and simplification of operator training. This paper focuses on the rationale for selection of GIS switchgear, and the design considerations that had to be addressed as the project moved from concept to installation to operation. Among the issues discussed are: space requirements for conventional and GIS equipment; arc resistant performance of GIS equipment; design commonality between 4.16 kV and 26.4 kV equipment; installation (cable issues, foundations, workspace, etc.); environmental considerations; total cost of ownership; reliability/availability; and operational experience.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.