Abstract

In a weak grid condition, the precise grid impedance estimation is essential to guaranteeing the high performance current control and power transfer for a grid-connected inverter. This study proposes a precise estimation method for grid impedance by PQ variations by employing the variation method of reference currents. The operation principle of grid impedance estimation is fully presented, and the negative impact of the phase locked loop is analyzed. Estimation error by a synchronization angle in the park`s transformation using the phase locked loop is derived. As a result, the variation method of reference currents for accurate estimation is introduced. The validation of the proposed method is verified through several simulation results and experiments based on a 2-kW voltage source inverter prototype.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.