Abstract
The major objective of this paper is the identification of the dominant modal responses of large scale power system dynamic simulations. The results of simulations are the angle-time responses of synchronous machine rotors. The rotor inertias coupled via transmission lines produce second order responses, whose damping factors and undamped natural frequencies are identified by a Model Adaptive Reference Control (MARC) system. The MARC identification system is applied successfully to the swing curves of a 1700 bus power system simulation to identify the local and intertie mode parameters. Specifically the sensitivity of modal damping due to power modulation of an HVDC tie is quantified. The low frequency interarea mode damping ratio (¢) is increased from 0.12 to 0.17 by the use of Frequency Sensitive Power Modulation, whereas the other parameters of the two modes were not affected significantly. Thereby the effectiveness of an External Control system on an HVDC transmission line is quantified. Previous evaluations had yielded only qualitative results.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.