Abstract

The paper deals with the power properties of three-phase circuits with unbalanced loads supplied from a three-wire line. It discusses various definitions of the apparent power in such circuits and shows that they cannot be interpreted in terms of any physical phenomena. The paper shows that the unbalanced power does not occur as an effect of the power oscillations and explains why this power does occur. The paper presents a decomposition of the supply current into the active, reactive, and unbalanced currents and shows that this decomposition can be considered as a fundamental for the comprehension of the power phenomena in such circuits and for the power factor evaluation. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.