Abstract

Accurate and timely detection of power quality (PQ) events is imperative for adequate corrective measures to be taken. This paper presents a method of PQ event detection development called joint triggering point detection (JTPD) scheme with a view to achieving a more accurate PQ event detection in a voltage waveform. The JTPD combines the advantage of cumulative sum (CUSUM) algorithm for the statistical distribution of a signal waveform and the discrete wavelet transform (DWT) for change-point detection. The performance of JTPD scheme using detection rate was compared with CUSUM and DWT schemes and based on the analysis, the detection rate of JTPD, CUSUM and DWT were 100%, 95% and 50% respectively. With this, the proposed approach outperformed CUSUM and DWT schemes by 5% and 50% respectively. Hence, the proposed approach is suitable for accurate detection of voltage dip, swell and interruption PQ events Keywords: Cumulative Sum, Discrete Wavelet Transform, Joint Triggering Point Detection, Power Quality, Voltage Waveform