Abstract

This research article presents the analysis of power losses in a three - phase distribution transformer, 100 kVA 22 kV-400/230V by using artificial neutral networks that can analyze the power losses in distribution transformer faster and use less variables than the original method. The measurement data were collected 100,000 sets at the transformer manufacturer factory by setting the current flow from 1% to 100% at temperature 30 °C, 35 °C, 40 °C, 45 °C, 50 °C, 55°C, 60 °C, 65 °C, 70 °C, and 75 °C to calculate the power losses in a distribution transformer. The collected data were divided 80,000 sets to use for training in order to find parameters of artificial neutral networks and 20,000 sets were used for the artificial neutral networks input in order to calculate power losses in a distribution transformer. From the power losses in the distribution transformer of artificial neutral networks testing compared with the calculated valued from the measurement. The percentage error was at the satisfactory level and can be applied to design the testing of power losses in the distribution transformer in the future.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.