Abstract

An oscillation blocking and re-opening scheme for distance protection in multisource oscillation scenes is proposed in this paper. First, the expression of measured impedance in multisource oscillation scenes is derived and the variation characteristic of the trajectory of measured impedance is analyzed. Then, according to the correlation between the measured impedance and the position of desynchronizing center, the desynchronizing center position factor (DCPF) is defined, and protection blocking and re-opening criterion based on DCPF is constructed. Real Time Digital Simulator test results demonstrate that the proposed scheme can effectively block the protection during oscillation even when fault occurs at the same time as the desynchronizing center appears, and re-open the protection quickly when a fault occurs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.