Abstract
This paper present results of tests conducted in the High Voltage Laboratory of the Ohio State University and deals with power frequency AC sparkover voltage measurement of small air gaps. Emphasis was placed on obtaining breakdown characteristics of electrodes and air gap separations that are representative of power lines 69 kV and below. Besides the customary rod-rod, rod-plane, and sphere-plane arrangements, other electrode configurations included various conductor sizes with conductor-rod, -plane, and -sphere arrangements and conductor-hot stick configurations with hook, puller, and wire brush accessories. It was found that the conductor size has a significant effect on the sparkover voltage. In addition, for the more practical electrode arrangement involving conductors, the sparkover voltages were greater than the rod-rod results in all but a few instances.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.