Abstract

Energy router (ER) is the key equipment in the construction of AC / DC hybrid distribution network in the future. Based on the characteristics of AC and DC ports and topological structure of ER, a steady-state model of ER with multi ports access was established, and a power flow model of AC / DC hybrid distribution network considering ER was constructed. Newton Raphson method combined with alternating iteration method was used to solve the problem. IEEE-33 was selected to calculate and compare the circular distribution network considering ER and the traditional AC distribution network. The results show that ER can improve the voltage level of nodes and reduce network loss in hybrid distribution network.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.