Abstract
To enhance the harmonic mitigation capability of the multi-pulse rectifier, this paper proposes a multi-pulse rectifier based on harmonic mitigation technology at DC link. The conventional 12-pulse rectifier does not meet the IEEE-519 standard and hence the active power factor correction technique is employed to mitigate the harmonics. The proposed system employs two diode bridge rectifiers, each followed by a SEPIC converter, by controlling the SEPIC converter inductor current, the input line current of the rectifier can be approximated to a sinusoidal waveform. A zigzag connected autotransformer is used as a phase-shift transformer in order to provide a phase shift and inherently blocks the zero sequence components. This method reduces the total harmonic distortion and also decreases the size of the system. The proposed configuration is analyzed and simulated in the MATLAB Simulink and also implemented in laboratory. The results show that the proposed method improves the power quality by reducing the total harmonic distortion (THD) in the input line current.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.