Abstract

This paper analyzes one of the most important power capture challenges of the DC series–parallel collection system, called the power curtailment losses. The wind speed difference between the series-connected turbines causes over- and under-voltage conditions in the output voltage of the MVDC (medium-voltage DC) converters of the wind turbine. The power curtailment losses caused by the upper-voltage tolerance levels of the MVDC converters of the wind turbines are analyzed considering a redundancy-based upper-voltage limiting condition. This analysis emphasizes the importance of choosing suitable voltage tolerance levels for the MVDC converters of wind turbines based on the wind farm configuration. The annual energy curtailment losses are quantified and evaluated by a comparative case study performed on a DC series–parallel-connected wind farm rated at 200 MW with the redundancy-based upper-voltage limiting condition.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.