Abstract

Models in high frequency range for underground power cabling system are the basis for the analysis of many condition diagnostic techniques, for instance, partial discharge (PD) monitoring. This paper focuses on modeling of power cable joints. A cascaded transmission line model is proposed for 10kV oil-filled PILC-PILC straight power cable joint in the frequency range of 300 kHz-800 MHz. It can be applied to interpret PD signal transmission and reflection behavior in power cable connections. The model is verified by S-parameter measurement.