Abstract

In this paper, postmortem aging investigations on insulation material of power transformers are presented. A methodology for taking paper samples in a systematical manner and a scheme for calculating an average degree of polymerization (DP) for the entire transformer out of the DP values of the individual paper samples will be shown. The typical DP profile in the axial direction of transformer coils will be explained using calculated distribution of losses within the coils of a 740-MVA generator stepup transformer. Further, correlations between the furan (2-FAL) concentration in the oil and the average DP of the investigated German GSU transformers and grid transformers are derived and compared with existing correlations.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.