Abstract

This paper deals with the postfault analysis of the operation of distance protective relays from the line terminals. The signals of the digital distance relays are processed in the offline regime with the aim of evaluating the particular relay operation case. First, the program enables imitating the fault-loop impedance measurements of the distance relays. Second, the two-end unsynchronized measurements of the relays are considered. The unknown synchronization angle is determined by using the developed noniterative procedure. Then, the distance to fault is calculated. It is applied for calculating the actual values of impedance for the line sections. Comparing the results of these two ways performs analysis of operation of the relays under resistive fault cases. The described postfault analysis algorithm has been tested with the fault data obtained from versatile Alternative Transients Program-Electromagnetic Transients Program simulations. The examples are reported and discussed

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.