Abstract

This paper presents a new method to obtain a voltage stability index for unbalanced radial distribution system. Voltage stability index (VSI) is used only for balanced radial distribution system. By using the sequence component, the unbalanced in distribution system could be simplified into a single-phase system. From the positive and negative sequence value, the voltage stability index for unbalanced distribution system can be obtained easily. The IEEE 15 bus single phase test systems which is modified into three phase balanced system, and the Surabaya Utara 20 kV three-phase radial distribution system are used to verify the sequence based on Catastrophe theory VSI sequence method. The results show that voltage stability index ranking by using negative and positive sequences based on Catastrophe theory VSI is exactly the same with single-phase simulation. This method also has less execution time than the sequence based VRI and sequence based VSI methods.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.