Abstract

Abstract Nucleate pool boiling heat transfer coefficients (HTCs) of 14 refrigerants are measured from a 19mm o.d. plain copper tube heated by a cartridge heater. All measurements are carried out in the pool temperature of 4∼25°C and in the heat flux of 10∼80kW/m2. Test results show that HTCs of R32, R125, R143a, R152a, and R410A are higher than those of R22. Especially, R32 showed the highest HTCs among all the refrigerants tested. As for R22 alternatives, HTCs of R410A are 50% higher than those of R22 while those of R407C are very similar to those of R22. It is also found that some of the popular pool boiling heat transfer correlations in the literature failed to predict the HTCs of newly developed alternative refrigerants. Hence, a dimensionless analysis is carried out in an attempt to develop a general correlation for all HTCs of pure refrigerants. Thus developed correlation showed an excellent agreement with all experimental data showing a mean deviation of 5.5%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.