Abstract

The paper describes a novel method for polyphase ground fault relaying with the help of a simple coincidence principle of the selected input quantities. The general principle of operation, actual design and performance results have been discussed. The relay operates correctly for all single line to ground faults, as well as double line to ground faults with the same reach in each case. For line to line faults and 3-phase faults the relay remains completely inoperative. Like other reported relays of the same category it has the advantages of insensitivity towards balanced overload and power swings in the transmission line. Moreover it has greater tolerance for arcing faults and is less susceptible to transient over-reach or maloperation due to other spurious signals. The relay is also completely directional in nature.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.