Abstract

The authors describe an extension of the point of collapse method developed for studies of AC systems to the determination of saddle-node bifurcations in power systems including high voltage direct current (HVDC) transmission. Bus voltage profiles are illustrated for an AC/DC test system. They significantly differ from the profiles of pure AC systems for typical system models. In particular, voltage dependent current order limits are shown to affect the voltage profiles and the loadability margin of the system. It is also shown that Hopf bifurcations, which are possible in purely AC lossless systems with second-order generator models, become plausible when the dynamics for the HVDC system are included. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.