Abstract

This paper proposes a new fault location technique for EHV double circuit transmission lines using synchronized current and voltage measurements from both ends. Double circuit lines faces difficulties in fault location due to mutual coupling. Modal transformation is used to decouple the coupled transmission line equations. Fault detection and location indices in terms of modal components of measured currents and voltages are derived. The transmission lines are modeled as equivalent π in the modal domain so as to compensate the effect of charging current. The proposed indices are tested by simulation in ATP and implementing the algorithm in MATLAB. The simulation results shows that the proposed method can effectively locate ground as well as phase faults in presence of fault resistance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.