Abstract

Direct contact membrane distillation (DCMD) supplied with waste heat was demonstrated for water recovery from saline demineralisation regeneration waste. The pilot plant was located at a gas fired power station which provided the <40°C waste heat and wastewater to the DCMD system with 0.67m2 of membrane area. The trial was operated over three months without replacing the membranes or module and achieved 92.8% water recovery. Flux was approximately 3L/(m2·h) and was dependant mostly on the waste heat temperature being supplied. Membrane fouling affected flux and thermal energy demand only at the very end of the trial. The system produced a high quality distillate product with average 99.9% dissolved solids rejection. Small amounts of ammonia and carbon dioxide however were found in the permeate. Membrane analysis post-trial revealed fouling was principally inorganic scale but organic matter on the membrane was also evident. Permeate side fouling was also observed, attributed to corrosion of the cooling heat exchanger. Based on the available energy for a continuously operating 500MW (electric) rated power station, the treatment potential was estimated at up to 8000kL/day, which is practical for supplying water to numerous industrial, residential or agricultural sites.