Abstract
To solve the problem that the voltage travelling wave protection at the AC bus is difficult to detect in the AC/DC interconnection network, a frequency protection principle of the line waveguide using the phenomenon of travelling wave catadioptric is proposed in this paper. According to the catadioptric phenomenon when the discontinuity of traveling wave impedance meets the wave, the fault area is identified by using the different refraction and catadioptric coefficients of faults inside and outside the region. In PSCAD/EMTDC environment, the AC-DC interconnection network model is established, and the protection principle is verified by MATLAB.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.