Abstract

Sulfur hexafluoride (SF6) is commonly used in gas insulated switchgears (GIS) as an insulating medium. When local overheating or partial discharge occurs in GIS, SF6 may be decomposed into various products including CO. In this paper, based on the photoacoustic (PA) effect of gas molecules, the infrared absorption line at 6380.318 cm−1 was chosen as the target line. An infrared laser with a center wavelength of 1567 nm was chosen as the light source, and a cantilever enhanced PA detector was used as the sensor; then, the experimental platform was constructed. The influence of the temperature and pressure on the infrared absorption coefficient of CO was analyzed. The relationship of the PA signal and the CO concentration under the background of SF6 and N2 were obtained. The results show that the temperature has a great influence on the CO absorption coefficient while the influence of pressure is negligible, and the temperature influential coefficient is about 5.0 × 10−6 cm−1/°C. The detection system has the highest signal-to-noise ratio when the frequency of the chopper is 40 Hz. Under N2 and SF6 background gases, there is a good linear relationship between CO concentration and pure PA signals. The minimum detection limit of CO in the background of N2 is 3.63 ppm, while it is 9.88 ppm in SF6. The different kinds of the background gases can influence the PA signals. The PA signals decrease with the increase of the temperature of the gas cell, and they also decrease with the increase of the pressure.

Highlights

  • Sulfur hexafluoride (SF6) is widely used in gas insulated switchgears (GIS), which are composed of a circuit breaker, disconnector, grounding switch, mutual inductor, lightning arrester, and outgoing terminal as an insulating medium due to its good electrical insulation and arc-extinguishing properties

  • When local overheating or partial discharge occurs in GIS, SF6 may be decomposed into various products including CO

  • The results show that the temperature has a great influence on the CO absorption coefficient while the influence of pressure is negligible, and the temperature influential coefficient is about 5.0 × 10−6 cm−1/○C

Read more

Summary

INTRODUCTION

Sulfur hexafluoride (SF6) is widely used in gas insulated switchgears (GIS), which are composed of a circuit breaker, disconnector, grounding switch, mutual inductor, lightning arrester, and outgoing terminal as an insulating medium due to its good electrical insulation and arc-extinguishing properties. There has been a study on CO detection using PAS gas detection technology, at the wave number of 4291.50 cm−1, using a distributed feedback (DFB) and a continuous wave (cw) laser diode with a high output power of 8 mW as the light source, which combine the wavelength modulation spectroscopy and second-harmonic detection techniques, achieving a minimum detection limit (MDL) of 9.8 ppm.. In March 2019, a study was carried out on a compact and sensitive mid-infrared all-fiber quartz-enhanced photoacoustic spectroscopy sensor for CO detection, where a MDL of 4.2 ppm was achieved, and similar to Ref. 20, it chose a mid-infrared laser whose wavelength is 2.33 μm. Under the condition that the power of the infrared laser is only about 10 mW, a MDL of 3.63 ppm in the N2 background and 9.88 ppm in the SF6 background were achieved

EXPERIMENTAL PRINCIPLE
The experimental platform
Pressure effect
OPTIMAL MODULATION FREQUENCY
The relationship between PA signals and CO concentration
System noise and the minimum detection limit
The effect of the background gas
Findings
VIII. CONCLUSION
Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call