Abstract
According to a mal-operation accident of differential protection which is caused by the effect of a switching-on transformer with no load on a parallel running transformer in a 35KV substation, the emergency and the development of transformer sympathetic inrush current was analysed from the aspect of the flux. And the three-phase differential current and their second harmonic component were obtained, which shows that the mal-operation wasn’t caused by the low second harmonic component in the differential current but by the changed transfer characteristics of the current transformer, which leads to an increase in the differential current.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.