Abstract
Abstract The non-transposition erection of transmission lines will lead to the imbalance of electrical parameters, which will affect the protection and automatic reclosing. The best phase sequence arrangement is determined by comprehensively considering the comprehensive indexes (current imbalance, secondary current, and recovery voltage) of double transmission un-transposed lines with shared towers. PSCAD/EMTDC electromagnetic transient simulation software is applied to build a typical 750kV transmission line model for simulation analysis, and the comprehensive indexes under different phase sequence arrangements are studied. The analysis reveals that the arrangement of phase sequence exerts a significant consequence of the comprehensive index. The findings indicate that the margin and different secondary current and recovery voltage indexes, double transmission un-transposed lines with shared towers can be erected in the same direction or in different phase sequences to reduce the current imbalance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.