Abstract

Here, the stability region of grid-connected VSC with phase locked loop (PLL) is estimated. First, the conservative stability region is derived via the classical Lyapunov method. Then an energy function is constructed as the general stable condition for the VSC system. Based on the constructed energy function, two estimation methods of the system stability region by approximation of phase trajectory are proposed. The stability regions by the proposed methods are less conservative than that by the classical Lyapunov method. A stability evaluation function for the initial states of the VSC system is further proposed based on the estimated stability region. Time-domain simulations verify the correctness of the proposed methods and the effectiveness of the stability evaluation function.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.