Abstract

The effects of system parameters and transformer sizes on phase-phase switching surges on 500-kV autotransformer- transmission line combinations when switched through the auto- transformer were investigated on a transient network analyzer. The results of the study are presented, including surge magnitude, waveshapes, and the line-neutral polarity components comprising the phase-phase surges. Phase-phase switching-surge frequency of occurrence data are illustrated.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.