Abstract

This paper describes the breaking ability of a small model of a fault current limiting circuit breaker (FCLCB), which consists of an air relay unit and a flux flow resistive type of a superconducting FCL unit with a high Tc B2223 bulk. Two Bi2223 elements were connected in series as an elementary FCL unit. Current carrying tests were performed for the elementary FCL unit to find the generating aspects of the flux flow resistance and the contact resistance. Current limiting and breaking performances were measured for the small model of the FCLCB that was constructed by connecting the elementary FCL unit with the relay contactor. It is confirmed that the apparent capability of the breaker unit is elevated by combination with the FCL unit. The FCL unit for the 6.6 kV power distribution systems was also designed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.