Abstract

To prevent improper design and construction of fire compartments through-penetration in buildings, and in order to reinforce public building safety management, all beams, pillars, ceilings, floors, doors, walls, and interior decorative materials must have fireproof properties. Moreover, cable conduits, water pipes, and air ducts located in through-penetration sites within buildings should be properly designed to block the spread of smoke and hot air, thus, reducing losses due to fire disasters. This study used common firestop materials, such as firestop sheets, mineral wool, and two-pack fire barrier foam to conduct 10-min surface burning tests on individual substrates. The flame spread distance and smoke per minute were measured and recorded in order to calculate the Flame Spread Index (FSI) and Smoke Developed Index (SDI). The results showed that all three firestop materials meet with the ASTM E84 Class A.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.