Abstract

Abstract In this paper, medium-temperature chiller with induction air-conditioning system is introduced. Several onsite measurements were carried out on temperature and relative humidity distribution and energy consumption in summer 2020 in order to study the potential performance when applied in hot summer cold winter zone. The performance test results show that (1) the indoor temperature and humidity both comply with the range of design parameters; (2) the corresponding indoor air dew point temperature is much lower than the supply air temperature of air inductive unit, which implies no condensed water or dew on surface of air inductive unit; (3) the performance of the circulation pump, extensive type air handling unit fan; and medium-temperature chiller has exceeded the requirements of national standards.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.