Abstract
Because of low cooling efficiency, it is usually difficult for a conventional carbon dioxide heat pump (CO2 HP) to meet the annual demands of cooling, heating, and domestic hot water (DHW) for a building. Thus, a hybrid solar-assisted CO2 HP, which integrates a solar thermal-driven absorption chiller with a conventional air-source CO2 HP, was developed. The technological solution for the integration is first presented. The experiment was then carried out to validate the calculated results of system design. The experimental result showed that the coefficient of performance (COP) of the hybrid HP operating in a conventional CO2 HP mode could reach 2.64. Further, system simulation showed that compared to the conventional CO2 HP, the hybrid CO2 HP can reduce electricity consumption by 13.7%. In addition, the exergy efficiency of the hybrid CO2 HP, and the influence of the environmental conditions on the COP were also discussed for performance evaluation. Finally, the feasibility of using the hybrid CO2 HP for realizing the net zero energy aim was confirmed through an energy balance analysis, based on the experimental and simulated results.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.