Abstract
Fresh air system is getting more and more important nowadays. The heat pump fresh air system based on the desiccant coated heat exchanger (DCHE) that can handle the latent and sensible load of fresh air efficiently has a large energy saving potential. To improve the performance of the heat pump fresh air system based on DCHE, in this paper, a control system based on PLC is established and the operation strategies of the system are investigated. An operation strategy including automatic control of the opening of the electronic expansion valve based on the suction superheat of the compressor, control of the switchover period based on the relative humidity of supply air, and control of compressor frequency based on evaporation and condensation temperature is established. By using the optimal operation strategies, the dehumidification rate and COP of the system can reach 4.42 kg/h and 6.2 in summer, compared with the unoptimized strategy it increased 8% and 25%, respectively. The two performance indices can reach to 3.04 kg/h and 6.98, with an increase of 89% and 78%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.