Abstract
This paper discusses the performance of cold storage using R32 refrigerant. R32 is one of the recommended refrigerant with the main advantage low ODP and GWP (Global Warming Potential) value of around 0 and 675. However, because of this refrigerant classified as a new refrigerant, the implementation is limited to air conditioning and heat pump. In this paper, R32 will be tested for cold storage applications. The cold storage performance will be studied about the achieved temperature, power consumption, cooling capacity and Coefficient of Performance without load. The testing was carried out in 2 ways, cold storage testing on a lab scale and direct testing on a 5 GT fishing boat. The performance results show that both tests on a lab scale and tests directly on a fishing boat without a load can reach a cold storage room temperature of -18oC. Meanwhile, the compressor power consumption supplied by photovoltaic is 0.653-0.776 kW. Based on the test results, shows that R32 has a positive possibility of being applied to cold storage.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.