Abstract
SYNOPSIS Poor stratification in Domestic Hot Water (DHW) storage tanks strongly reduces the performance of solar collectors. As stratification disturbances are frequent particularly in medium-large size plants, it is more realistic to consider fully mixed tanks. Multi-tank storage systems can work well even if stratification is not assured, provided that suitable connections in the tanks allow different thermal levels in every tank, forming a kind of forced stratification. Three control strategies of multi-tank systems have been simulated and compared with single-tank. Annual results demonstrate that multi-tank is a good solution in the absence of stratification. Different performances of multi-tank systems are also discussed.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.