Abstract

The performance of the energy consumption of an electronic valve and a classical thermostatic valve has been compared when these expansion valves are adopted in a vapour compression plant subjected to a cold store. The main aim is to verify experimentally which type of expansion valve would be preferable from energy point of view when a classical thermostat or a fuzzy logic algorithm are used as the control system for the refrigeration capacity. The fuzzy logic-based control is able to modulate continuously the compressor speed through an inverter. The results show that with a fuzzy algorithm, the thermostatic expansion valve allows an energy saving of about 8% in comparison with the electronic valve. When on–off control is used, the electric energy consumption obtained both with the electronic valve and with the thermostatic valve is comparable. Copyright © 2006 John Wiley & Sons, Ltd.