Abstract

This paper presents the results of investigations on the performance of nonceramic insulators in tropical field conditions. Six different types of 33 kV insulators (silicone rubber, EPDM composite, porcelain, and RTV coated porcelain) were installed at six different test sites exposed to marine, industrial and clean environments in Sri Lanka and Tanzania. The visual scrutiny, hydrophobicity class (HC) and surface conductivity were used for the evaluation of the field performance. The silicone rubber and RTV coated insulators preserved the hydrophobic properties although some biological growth was found on them. The EPDM insulators showed distinct surface changes. At the same time, damage due to dry-band arcing appeared on the porcelain insulators exposed to marine pollution.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.