Abstract

Abstract The thermal-hydraulic performance of microchannel condensers with open-cell metal foams to enhance the air-side heat transfer is investigated in this paper. Three different copper metal foam structures with distinct pore densities (10 and 20 PPI) and porosities (0.893 and 0.947) were tested. A conventional condenser surface, with copper plain fins, was also tested for performance comparison purposes. The experimental apparatus consisted of a closed-loop wind tunnel calorimeter and a refrigerant loop, which allowed the specification of the mass flow rate and thermodynamic state of R-600a at the condenser inlet. The experiments were performed at a condensing temperature of 45 °C. The air-side flow rate ranged from 1.4 × 10 −3 to 3.3 × 10 −3 m 3 /s (giving face velocities in the range of 2.1–4.9 m/s). The heat transfer rate, the overall thermal conductance, the Colburn j -factor, the friction factor and the pumping power were calculated as part of the analysis.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.