Abstract
Ferroresonant overvoltages have been recognized as a threat to arresters installed on underground distribution systems. Extensive tests have been performed to evaluate the thermal and electrical performance of MOV arresters exposed to this duty. Arrester discharge currents were found to be small and arrester heating is slow. The eventual temperature rise and the potential for thermal instability depends greatly on the type of arrester. Arrester designs which promote better heat dissipation to the ambient are shown to reach an acceptable steady-state temperature when exposed to ferroresonance of indefinite duration.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.