Abstract

This study examines the applicability of the ice storage systems in the small commercial refrigerated showcases through experimental analysis. R-404A is used as the working fluid and various influence of parameter settings and improvements, are discussed in details. In the ice storage system, the condenser is changed from air-cooling (refrigeration mode) to an immersion type that is placed in an ice storage tank, the corresponding condensing temperature and pressure are reduced appreciably. This increased the efficiency and can effectively reduce the peak power consumption. The reduction of the condensing temperature and pressure increased the coefficient of performance (COP) from 3.6 (refrigeration mode) to 6.35 (melting mode), effectively enhancing the refrigeration efficiency. The results indicated that the ice storage system could effectively increase the coefficient of performance from 3.6 to 6.35 during ice melting when compared to the conventional refrigeration system. It also can shift approximately 35% of the power during peak hours and lower the energy cost by USD$ 17.13 per month.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.