Abstract

An experimental study on the performance of calcium chloride-ammonia adsorption system is described. A single bed water cooled condenser adsorption refrigerator prototype, which utilises calcium chloride-ammonia pair has been developed and tested in the laboratory. Experiments have been conducted for desorption temperatures of 100 °C with desorption time varying from 1 to 4 hours. An electric tape heater and a timer were used to perform the experiments. The adsorption temperature profile, adsorption rate and prototype performance have been analysed and discussed. The tested heating and desorption temperature of 100 °C and heating and desorption time of 1 to 4 hours was able to create a cooling effect of the cold chamber of the prototype of between -0.8 to 8.3 °C, which is adequate for vaccine storage requirement of 2 to 8 °C. The estimated Coefficient of Performance of the system ranges between 0.025 and 0. 076.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.