Abstract
ABSTRACT: Colfax, WA, operates an aerated lagoon to achieve compliance with its National Pollutant Discharge Elimination System (NPDES) permit, which currently requires biochemical oxygen demand (BOD) and total suspended solids (TSS) removal. However, ammonia removal may soon be required, and Colfax is considering a nitrifying trickling filter (NTF) that would allow them to also maintain the lagoons. To obtain data from which to ultimately design a full‐scale system, a four‐year NTF pilot study was performed. Results demonstrated that an NTF would be an effective, reliable NH3 removal method and could produce effluent NH3 concentrations < 1.0 mg/L. NTF performance was characterized by zero‐ and first‐order kinetics; zero‐order rates correlated with influent NH3 concentrations and mass load. Utilizing data from these investigations it was determined that the pilot NTF could be reduced by 19%, which demonstrates the value of pilot testing. Finally, pilot data was evaluated to provide a data set that will be useful to engineers designing full‐scale NTFs.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.