Abstract

The authors describe the experience of the Bonneville Power Administration in building and operating a long-term, unattended station to measure electric fields and air ions from the Pacific NW/SW HVDC (northwest/southwest high-voltage direct current) Intertie. The major emphasis is on the performance of the unipolar ion counters, as these have been the most difficult type of instrument to incorporate in an outdoor measurement station. Based on this experience, if heat is properly applied to the ion counter and good procedures are used for regular calibration and maintenance of all the instrumentation, then electric field and air ion instrumentation can be operated unattended in an outdoor environment. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.