Abstract

We report on test results for a single phase, 60-Hz, 13.8 kV/6.9 kV, 1-MVA high temperature superconducting (HTS) transformer which was completed in February, 1998. This transformer models in many ways a full scale section of a 30-MVA HTS commercial transformer design. The transformer windings are cryocooled in the range of 25 K and are made with a low-cost, surface-coated BSCCO-2212 conductor. Heat leaks are reduced using a liquid nitrogen thermal ballast and reservoir. The use of high temperature superconductors can substantially reduce transformer losses, weight, size, noise and potential fire and environmental hazards. Designs promise stable operation through faults without thermal degradation, and at temperatures that allow efficient and reliable refrigeration.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.