Abstract

In this study, the performance of an R22 refrigeration system of 9.6 kW cooling capacity injecting vapor and liquid refrigerant to compressor inlet through accumulator is analyzed at high compression ratio experimentally. Results obtained in this study are compared and discussed for better performance of refrigeration system with respect to the injection type and ratio. In vapor injection, the COP decreased with increasing injection ratio while in the liquid injection, the COP increased up to 10% of injection ratio and decreased beyond that. Thus, the liquid injection up to 10% is recommended at high compression ratio in order to minimize the performance decrease and extend operating range of a refrigeration system. In addition, the subcooling for liquid injection could be considered as a proper parameter to control the injection for the reliable operation in the liquid injection case.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.