Abstract
Gas turbine performance is very sensitive to the ambient air conditions, particularly in hot and arid climates. Various turbine inlet air cooling (TIAC) techniques including mechanical vapor compression and lithium bromide-water absorption refrigeration systems are used in several locations worldwide. This work concerns a comparative study using mass and energy balances and cost analysis of several cooling technologies coupled with a typical gas turbine under Riyadh weather conditions. The results are expressed in terms of yearly variations of power output, fuel consumption, and thermal efficiency of the gas turbine unit. They also include the total and operating costs and the payback period for each configuration of TIAC systems. The study proposes first systematic approaches to determine the air cooled temperature at the compressor inlet and the corresponding cooling capacity for the considered TIAC systems. The optimum values of such air cooled temperature and cooling capacity are found to be 8 °C and 36 kW/m3 s−1, respectively. The comparative study shows that using the media evaporative cooling, the simple mechanical vapor compression or the single-effect H2O-NH3 absorption cooling systems are not recommended. However, the sub-cooling multistage compressor system coupled with a wet cooled condenser and the single-effect LiBr-H2O-absorption refrigeration systems show better performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.