Abstract

The aim of this study was to investigate the thermal performance of the hydronic radiant baseboards currently used for space heating in built environments. The presently available equations for determination of heat outputs from these room heaters are valid for a certain height at a specific temperature range. This limitation needed to be addressed as radiant baseboards may be both energy and cost efficient option for space heating in the future. The main goal of this study was therefore to design an equation valid for all baseboard heights (100–200 mm) and excess temperatures (9–60 °C) usually used in built environments.The proposed equation was created by curve fitting using the standard method of least squares together with data from previous laboratory measurements. It was shown that the predictions by the proposed equation were in close agreement with reported experimental data. Besides, it was also revealed that the mean heat transfer coefficient of the investigated radiant baseboards was about 50% higher than the mean heat transfer coefficient of five conventional panel radiators of different types.The proposed equation can easily be used or programed in energy simulation codes. Hopefully this will help engineers to quantify more accurately the energy consumption for space heating in buildings served by radiant baseboards.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.