Abstract

The objective of this work is to develop a computer simulation program to evaluate the performance of solar-assited combined ejector absorption (single-effect) cooling system using LiBr/H2O as a working fluid and operating under steady-state conditions. The ejector possess no moving parts and is simple and reliable, which makes it attractive for combination with single-stage absorption cycle for further improvement to the system's performance. In this research, improvement to the system is achieved by utilizing the potential kinetic energy of the ejector to enhance refrigeration efficiency. The effects of the entrainment ratio of the ejector, operating temperature, on the thermal loads, and system performance have been investigated. The results showed that the evaporator and condenser loads, post-addition of the ejector, is found to be permanently higher than that in the basic cycle, which indicates a significant enhancement of the proposed cycle and the cooling capacity of the system increasing with the increase in evaporator temperature and entrainment ratio. The COP of the modified cycle is improved by up to 60 % compared with that of the basic cycle at the given condition. This process stabilizes the refrigeration system, enhanced its function, and enabled the system to work under higher condenser temperatures.